All questions and answers are based on the 2008 NEC. Q. Is GFCI protection required for receptacles above the counter of a break room in an office building? A. If the break room has a sink and ...
Explanation: Section 210.8(B)(7) now requires GFCI protection for receptacles that supply fixed or stationary appliances when either the receptacle or the appliance is located within 6 ft of the sink.